The inverter is the brain of a rooftop solar system, and when something is wrong it says so on its screen or app. The trouble is that the messages are short and technical: "Grid OV", "Riso Low", "GFCI", "No Utility". Most owners do not know whether to worry. This guide explains the errors we see most often on systems in Madhya Pradesh and Chhattisgarh, what usually causes them and what you can safely do. Exact wording differs by brand, so check your manual too.
Key Takeaways
- Grid errors (voltage, frequency, no grid) are usually caused by the supply, not your system.
- Isolation and earth-leakage errors point to wiring or moisture and need a technician.
- Overtemperature means the inverter needs shade and air.
- Never open the inverter or DC junction boxes yourself.
- Note the error, the time and a photo before you call.
Grid overvoltage ("Grid OV", "AC Overvoltage")
What it means: the grid voltage at your meter has gone above the limit the inverter is allowed to work at, so it disconnects for safety.
Why it happens: it is common on rural and semi-urban feeders, especially around midday on sunny days when many rooftop systems export and local demand is low. A long or thin cable between the inverter and the meter adds to the voltage the inverter sees.
What to do: if it happens occasionally and clears on its own, it is a supply issue. If it happens every sunny afternoon, call your installer. They can check the AC cable size, tighten connections and, within the limits allowed by the DISCOM, review the inverter's grid settings. Persistent high voltage should also be reported to your MPPKVVCL, MPMKVVCL or CSPDCL office, because it affects your appliances too.
Grid undervoltage or frequency error
What it means: the grid voltage or frequency is outside the allowed band. The inverter disconnects and reconnects automatically once the supply is normal.
What to do: usually nothing. Frequent occurrences in the evening or during storms are a supply problem. If it shows on a clear day while the supply looks fine, ask your installer to check the AC connections.
No grid ("No Utility", "Grid Lost", "Islanding")
What it means: the inverter cannot see the grid. During a power cut this is normal: an on-grid inverter must switch off so that line workers are safe.
What to do: if there is a power cut, wait. If the house has power but the inverter still says no grid, the AC breaker between the inverter and the meter may have tripped or a connection may be loose. Check that the solar AC breaker is on; if it trips again, call for service.
Isolation fault ("Riso Low", "PV Insulation Fault")
What it means: before starting each morning, the inverter tests whether any DC wiring is leaking to earth. If the resistance is too low, it refuses to start.
Why it happens: a damaged cable, water in a connector or junction box, a cracked panel back-sheet, or cables rubbing on a sharp edge. It is most common in the monsoon and on dewy winter mornings, and sometimes clears as the day dries.
What to do: do not touch the DC side. If the error clears by mid-morning and returns only on wet days, book a service visit soon. If the system will not start at all, call immediately. A technician will test each string to find the faulty part.
Earth leakage ("GFCI", "Residual Current", "Leakage Current")
What it means: while running, the inverter detected current leaking to earth and shut down.
What to do: treat it as a safety issue. Switch the system off at the AC and DC isolators as your installer showed you, keep people away from the roof wiring, and call for service. Common causes are moisture in connectors, damaged cables and, sometimes, poor earthing.
Overtemperature ("Over Temp", "Derating")
What it means: the inverter is too hot, so it reduces output or stops until it cools down.
Why it happens: an inverter mounted in direct afternoon sun, in a closed room, or with a fan or vents blocked by dust. It is common in May and June across central India.
What to do: make sure the inverter has shade and open space around it, clean dust from the vents with a dry cloth while it is off, and ask your installer about a canopy or relocation if the error is frequent.
PV overvoltage or string errors
What it means: the DC voltage from the panels is too high or a string is not producing as expected. Overvoltage can happen on very cold, bright mornings if the system was designed close to the limit; string errors suggest a disconnected or faulty string.
What to do: note when it occurs and call your installer. These need checking against the system design.
Communication or Wi-Fi errors
If the app shows "offline" but the inverter screen shows normal generation, the problem is only the Wi-Fi or data logger. Your system is still producing. Restart the router, check the Wi-Fi password has not changed, or ask your installer to reconnect the logger.
What to note before you call
- The exact error message or code on the screen.
- The date and time, and whether it clears on its own.
- The weather — sunny, cloudy, raining, early morning.
- Whether the house had power at the time.
- A photo of the inverter screen and, if possible, the app's daily graph.
This lets the technician diagnose most problems before the visit and bring the right parts.
What not to do
- Do not open the inverter, combiner box or DC junction boxes.
- Do not unplug DC connectors while the system is running; DC arcs are dangerous.
- Do not spray water on the inverter or wiring.
- Do not keep resetting a breaker that trips repeatedly.
Need help?
Sunvera Energy services systems from its offices in Pichhore, Gwalior, Balaghat and Bilaspur. WhatsApp a photo of the error to +91 77103 07937 and we will tell you whether it is a supply issue or needs a visit.
Frequently Asked Questions
Because the grid voltage at your meter has risen above the inverter's safe limit, often on rural feeders when many rooftop systems export and demand is low. If it happens daily, ask your installer to check the AC cable and connections, and report high voltage to your DISCOM.
The inverter found DC wiring leaking to earth during its start-up test. Common causes are water in a connector, a damaged cable or a cracked panel back-sheet. It is common on wet mornings. Do not touch the DC side; book a technician.
Yes. An on-grid inverter must switch off when the grid fails so line workers are safe. It restarts automatically when power returns. For backup during cuts, you need a hybrid system with a battery.
Check the inverter screen. If it shows normal generation, only the Wi-Fi or data logger has disconnected and the system is still producing. Restart the router or ask your installer to reconnect the logger.