Solar for cold storage makes use of the two things these buildings have in abundance: vast unused sheet roofs and a compressor load that never switches off. Warehouses add daytime handling, lighting and office loads. Sunvera Energy designs rooftop plants of 50–300 kW for cold storages near mandis — Guna, Shivpuri, Bilaspur, Korba — and for logistics and storage warehouses across Madhya Pradesh and Chhattisgarh, using non-penetrative mounting so the roof stays watertight. Sunvera's 75 kW warehouse plant in Bilaspur is a working example of the approach.
Why cold storages and warehouses suit solar
A potato, onion or fruit cold storage near a mandi keeps its chambers at 2–4 °C or below for months. The refrigeration compressors, evaporator fans and condenser fans run day and night, and the load rises in the hottest months — exactly when solar generation is strongest. Warehouses add forklifts' charging, conveyors, lighting and air-conditioned offices during working hours. Both sit under large, flat, unshaded sheet roofs with no other use. A plant sized to the daytime portion of the load is consumed on site, saving ₹8–10 a unit on commercial or industrial tariffs.
Sizing to a 24-hour load
Because a cold storage's load continues at night, the right plant size is set by the daytime base load, not the total. Sunvera looks at twelve months of bills and the meter's load data: if the compressors draw 80 kW through a summer day, a plant of roughly 80–100 kW can be absorbed on site, and the night load continues from the grid. Seasonal patterns matter — a potato store loads in February–March and runs hardest through summer; a fruit store may peak differently — so generation and load are modelled month by month.
| Facility | Daytime load | Suggested plant | Roof needed | Installed cost |
|---|---|---|---|---|
| Small cold room / pack-house | 15–30 kW | 20–30 kW | 2,000–3,000 sq ft | ₹10–14 lakh |
| Mandi cold storage, 3,000–5,000 MT | 60–120 kW | 75–120 kW | 7,500–12,000 sq ft | ₹33–58 lakh |
| Logistics warehouse | 30–80 kW | 50–100 kW | 5,000–10,000 sq ft | ₹22.5–50 lakh |
| Large cold chain hub | 150+ kW | 150–300 kW | 15,000+ sq ft | on design |
Our 75 kW warehouse plant in Bilaspur
In Bilaspur, Sunvera installed a 75 kW on-grid rooftop plant on a warehouse sheet roof, using non-penetrative mounting and a three-phase inverter system with CSPDCL net metering. A plant of this size in Bilaspur generates roughly 1,05,000–1,15,000 units a year, offsetting ₹8–9 lakh of electricity annually at commercial tariffs — a payback of around four years before accelerated depreciation. The project is described on the projects page.
Engineering on sheet and insulated roofs
- No drilling. Clamps grip trapezoidal or standing-seam sheet profiles; on insulated sandwich-panel roofs of cold chambers, rail systems are chosen that do not compromise the insulation.
- Load check. The roof and purlins are assessed for the 15–20 kg per sq m added load and regional wind loads before layout.
- Heat benefit. Panels shade the roof, slightly reducing heat gain into the building — a small but real help to the refrigeration load in summer.
- Access and cleaning. Walkways and a water point for cleaning without stepping on panels; dust from mandi traffic makes regular cleaning essential.
- Protection. DC and AC protection, surge arresters, earthing and lightning protection, with inverters placed in a shaded, ventilated spot.
Why summer matters most for cold storage
Refrigeration load rises steeply with outside temperature. In April–June, when Guna, Shivpuri or Bilaspur reach 42–46 °C, condensers work hardest and compressors run longest — and those are also the months of longest, clearest days. A cold storage's solar plant therefore produces most when the facility needs most, which keeps self-consumption high even with the 24-hour base load. Panels also shade the roof slab, trimming heat gain into the building slightly; on large stores this small effect adds up over a summer.
Hybrid backup for perishable stock
A long outage in summer can cost a cold storage far more than its electricity bill, as chamber temperatures rise and produce spoils. Most stores rely on a large DG set for this. Where outages are frequent, a hybrid section with a lithium battery can carry the control systems, evaporator fans and monitoring through short cuts so the generator starts less often, and keep alarms and data logging alive at all times. Compressors themselves are usually too large to run on battery economically; the design keeps them on grid, solar and generator, and uses the battery only where it adds real protection.
Returns and depreciation
At ₹9 a unit, a 100 kW plant generating 1.45–1.5 lakh units a year saves about ₹13 lakh annually against an installed cost of ₹45–50 lakh — a simple payback of about 3.5–4 years. Profit-making cold storages and warehouse operators can claim accelerated depreciation on the plant, reducing the effective cost further; confirm the current rate with your chartered accountant. Plants are financed through bank term loans where needed, and the annual saving usually covers most of the instalment.
Approvals and maintenance
Applications go to MPMKVVCL or MPPKVVCL in Madhya Pradesh and CSPDCL in Chhattisgarh with a single-line diagram, structural certificate, inverter certificates and, above set capacities, electrical-inspector approval. Sunvera prepares every document; approvals usually take six to ten weeks. The O&M contract covers cleaning matched to the site's dust level, quarterly inspections and remote monitoring with a monthly generation report. Send twelve months of bills and your roof dimensions to +91 77103 07937 for a sized proposal.
Frequently Asked Questions
Yes. Compressors run around the clock and hardest in summer, when solar generation peaks. A plant sized to the daytime base load is consumed on site, saving ₹8–10 per unit; a 100 kW plant saves about ₹13 lakh a year for ₹45–50 lakh installed.
Roughly 10 kW per 1,000 sq ft of usable, unshaded roof, so a 10,000 sq ft roof can carry about 100 kW. The right size is set by the daytime load, not the roof; Sunvera models both before recommending.
No. Non-penetrative clamps grip the sheet profile, and on insulated sandwich-panel roofs rail systems are chosen that do not compromise the insulation. The roof's load capacity is checked before design.
Yes — a 75 kW on-grid rooftop plant on a warehouse sheet roof in Bilaspur, with non-penetrative mounting and CSPDCL net metering. It generates roughly 1,05,000–1,15,000 units a year.
Partly. Compressors are usually too large to run economically on battery, so they stay on grid, solar and the DG set. A hybrid section with a lithium battery can carry controls, evaporator fans, alarms and temperature logging through short cuts, so the generator starts less often and monitoring never stops.
Typically 3.5–4 years at commercial tariffs of about ₹9 per unit, before accelerated depreciation, which shortens the effective payback for profit-making operators. The plant then runs for 25 years or more.
Written generation estimate, exact price after subsidy and bank-finance options — no obligation.